Light Duty Fire Rated Cables
Light Duty 500 Volt Range
No. & Conductor Size | Current Ratings – Bare |
Served (LSF) | Volt Drop | Core Resistance @20 deg C |
Coil Length Typical |
Earth Fault Loop Impedance |
Cable Dia – Bare |
Served (LSF) | Approx Weight – Bare |
Served (LSF) | |
CableRef CC (Bare) CCM (LSF) |
Sq/mm | A | A | mV/A/m | Ohms/km | m | Ohms/km | mm | mm | kg/km | kg/km |
2 L 1 | 2×1.0 | 17.5 | 19.5 | 42 | 18.1 | 1100 | 26.2 | 5.1 | 6.4 | 104 | 125 |
2 L 1.5 | 2×1.5 | 22.5 | 25 | 28 | 12.1 | 800 | 18.3 | 5.7 | 7 | 130 | 153 |
2 L 2.5 | 2×2.5 | 30 | 33 | 17 | 7.4 | 580 | 11.8 | 6.6 | 7.9 | 179 | 205 |
2 L 4 | 2×4.0 | 40 | 44 | 10 | 4.6 | 450 | 7.8 | 7.7 | 9.2 | 248 | 287 |
3 L 1 | 3×1.0 | 15 | 16.5 | 36 | 18.1 | 800 | 25.3 | 5.8 | 7.1 | 135 | 159 |
3 L 1.5 | 3×1.5 | 19 | 21 | 24 | 12.1 | 650 | 17.6 | 6.4 | 7.7 | 168 | 193 |
3 L 2.5 | 3×2.5 | 25 | 28 | 14 | 7.4 | 500 | 11.4 | 7.3 | 8.8 | 224 | 261 |
4 L 1 | 4×1.0 | 14.5 | 16 | 36 | 18.1 | 700 | 24.8 | 6.3 | 7.6 | 161 | 187 |
4 L 1.5 | 4×1.5 | 19 | 21 | 24 | 12.1 | 550 | 17.2 | 7 | 8.3 | 202 | 230 |
4 L 2.5 | 4×2.5 | 25 | 28 | 14 | 7.4 | 400 | 11.0 | 8.1 | 9.6 | 278 | 319 |
7 L 1 | 7×1.0 | 10 | 11 | 42 | 18.1 | 600 | 24.1 | 7.6 | 9.1 | 233 | 271 |
7 L 1.5 | 7×1.5 | 12.5 | 14 | 28 | 12.1 | 480 | 16.6 | 8.4 | 9.9 | 291 | 333 |
7 L 2.5 | 7×2.5 | 17 | 19 | 17 | 7.4 | 350 | 10.4 | 9.7 | 11.2 | 407 | 455 |
Please contact us for the relevant datasheet for the 2-core range here;
- Light Duty 2 Core
Please contact us for the relevant datasheet for the 3-core range here;
- Light Duty 3 Core
Please contact us for the relevant datasheet for the 4-core range here;
- Light Duty 4 Core
Please contact us for the relevant datasheet for the 7-core range here;
- Light Duty 7 Core